The influence of transformers, induction motors and fault resistance regarding propagation voltage sags = Propagación de Huecos de Tensión: La influencia de transformadores, motores de inducción y resistencias de falla en relación con la propagación de huecos de tensión
Articles
Electronic International Standard Serial Number (EISSN)
2248-8723
abstract
This article presents an analysis of voltage sag propagation. The ATPDraw tool was selected for simulating the IEEE 34 node test feeder. It takes into account both voltage sags caused by electrical fault network, as well as voltage sag propagation characteristics caused by induction motor starting and transformer energising. The analysis was aimed at assessing the influence of transformer winding connections, the impedance of these transformers, lines and cables, summarising the effects on disturbance magnitude and phase. The study shows that the influence of an induction motor on voltage sag propagation results in increased voltage sag severity. Voltage sags caused by induction motor starting and transformer energising have no zero-sequence component, so they are only affected by type 3 transformers. The influence of fault resistance on voltage sag magnitude and phase characteristics is examined and some aspects of interest in characterising these electromagnetic disturbances is identified. Disponible online: http://www.scielo.org.co/scielo.php?script=sci_arttext&pid=S0120-56092011000500021&lng=es&nrm=iso
Classification
keywords
power quality; voltage sag propagation; voltage dip causes; transformer connection